Six single-ended impedance-based methods for estimating fault distance.
In Detego
All single-ended impedance-based fault location methods start from the same circuit equation. Looking from the relay terminal into a faulted line of total positive-sequence impedance , the measured loop voltage is:
Faulted line voltage equation
Where
The first term is the voltage drop across the line up to the fault point. The second term is the voltage drop across the fault resistance.
If the fault resistance were zero (a bolted fault), solving for would be trivial: . In practice, fault resistance is never zero -- arc resistance, tower footing resistance, and vegetation contact resistance all contribute. The term contaminates the measurement and causes errors in the distance estimate.
Each algorithm below uses a different strategy to eliminate or minimise the influence of fault resistance. They range from the simplest (Reactance) to the most sophisticated (Eriksson, Novosel), trading complexity for accuracy under increasingly difficult conditions.
Distance vs time — the reactance method produces a time-varying distance estimate. During the fault window, the stable portion is averaged to produce the final result.
The reactance method is the simplest fault location technique. It exploits the fact that fault resistance is purely real: it contributes only to the resistive component of the measured impedance and has zero imaginary part. By extracting only the imaginary part (reactance) of the loop impedance ratio, the fault resistance term is eliminated -- provided the fault current is in phase with the relay current .
Reactance method (IEEE C37.114)
Where
The numerator is the measured loop reactance. The denominator is the total line reactance. Their ratio gives the per-unit distance.
When It Works Well
Limitation: When and are not in phase -- due to remote infeed, load flow, or non-homogeneous source impedances -- the term has a non-zero imaginary part that leaks into the reactance measurement, causing distance error proportional to fault resistance.
The Takagi method improves on the reactance method by using superimposed current (also called incremental current) to cancel the fault resistance term. The superimposed current is the difference between the fault-period current and the pre-fault current. In a homogeneous system, the superimposed current is in phase with the total fault current , which makes it an effective proxy for eliminating the resistance contribution.
Takagi method
Where
Substituting the voltage equation into the numerator gives two terms: the line impedance term and the fault resistance term. The fault resistance term becomes . Since is real and is approximately in phase with (in a homogeneous system), the product is approximately real, and its imaginary part is approximately zero. The fault resistance contribution vanishes.
The Takagi method requires pre-fault data to compute the superimposed current. The pre-fault phasors are extracted from a DFT window before fault inception. If no fault inception time is available (either auto-detected or user-specified), the method cannot be used. It works for all fault types (ground, phase-phase, and three-phase).
The Modified Takagi method replaces the superimposed current with zero-sequence current as the reference for cancelling fault resistance. The zero-sequence current is approximately in phase with the fault current for ground faults, serving the same purpose as the superimposed current in the standard Takagi method -- but without requiring any pre-fault data.
Modified Takagi method
Where
Using the residual current 3I_0 = I_a + I_b + I_c gives the same result -- the factor of 3 appears in both numerator and denominator and cancels.
Applicability: Ground faults only (SLG and DLG). For phase-to-phase faults without ground involvement, zero-sequence current is zero and the method is undefined. No pre-fault data is required, making it useful when fault inception timing is unavailable.
Angle Correction
The Eriksson method uses knowledge of the source impedances at both terminals to formulate a quadratic equation in . By incorporating the system topology, it can correctly handle non-homogeneous systems where the Takagi method loses accuracy.
Eriksson quadratic
Where
The six coefficients are computed from the loop phasors and system impedances. Define the auxiliary complex quantities:
Eriksson coefficients
Where
The quadratic yields two roots. The physically meaningful root is selected by checking which value falls in the range . If both roots are valid, the root closest to the Takagi estimate is preferred as a consistency check. If neither root is in range, the result is flagged as unreliable.
Requirements: Pre-fault data (for ) and source impedances and at both terminals. These are typically estimated from fault studies or relay settings.
The Novosel method operates in the positive-sequence domain, which eliminates dependence on fault type and zero-sequence compensation. It uses an iterative approach with a distribution factor to estimate the total fault current, then explicitly solves for both fault distance and fault resistance.
Positive-sequence voltage equation
Where
The distribution factor estimates what fraction of the total fault current flows from the local terminal, based on the network impedances:
Positive-sequence distribution factor
Where
The fault current is then estimated as . Since depends on , and depends on , the solution is iterative.
The algorithm proceeds as follows:
Closed-form m update
Convergence is typically achieved within 3--5 iterations for well-conditioned systems. The method explicitly produces both and , which is useful for validating the result.
Requirements: Source impedances and . Works for all fault types because it uses positive-sequence quantities exclusively.
The radial method is the simplest possible fault location technique. It computes the fault distance as the ratio of the measured loop impedance magnitude to the total line impedance magnitude — the apparent impedance approach.
Radial method
Where
Unlike the reactance method (which uses only the imaginary part), the radial method uses the full impedance magnitude. This means fault resistance is not separated — any fault resistance adds directly to the measured impedance and inflates the distance estimate. The method reports a fault resistance of zero because it cannot distinguish line impedance from fault resistance.
When to Use
All algorithms (except Novosel, which uses positive-sequence quantities) require a measurement loop that selects the appropriate voltage and current phasors based on fault type. The loop selection follows IEEE C37.114.
| Fault Type | Loop Voltage | Loop Current |
|---|---|---|
| SLG-A | ||
| SLG-B | ||
| SLG-C | ||
| LL-AB | ||
| LL-BC | ||
| LL-CA | ||
| DLG-AB, DLG-BC, DLG-CA | Dominant faulted phase (e.g. ) | |
| 3-Phase | Any phase-phase (e.g. ) | Corresponding current (e.g. ) |
Phase-phase loops inherently cancel the zero-sequence component and do not use compensation. For line-to-line faults without ground involvement, these loops are the natural choice.
For double line-to-ground (DLG) faults, the phase-to-ground loop of the dominant faulted phase (the phase carrying the highest fault current) with compensation provides the most accurate fault location. The phase-to-phase loop between the two faulted phases does not account for the zero-sequence ground return path, leading to significant overestimation. This approach is consistent with how numerical distance relays handle DLG faults internally (e.g., Schneider P43x configures PG loops for 2-phase-to-ground measurement).
Zero-sequence compensation factor
Where
k_0 is a complex number. Typical values for overhead lines: magnitude 0.5--0.7. For cables: magnitude 0.3--0.5.
Different relay manufacturers use different input conventions for zero-sequence compensation. All are mathematically equivalent and convertible to the standard used internally.
The user provides and as magnitude and angle. The compensation factor is computed as:
Standard k_0 from impedances
Where
Used by SEL (auto mode), ABB (KN computation). This is the default input mode.
The user enters directly as magnitude and angle. No conversion is needed -- the value is used as-is. This matches SEL manual mode (k0M1), ABB KN, Siemens K0, and Schneider kG (Method 1).
Siemens relays (e.g. 7SA612) express the compensation as two separate real/reactive ratios. The conversion to the standard complex is:
Siemens ratio conversion
Where
RE/RL and XE/XL are dimensionless ratios. Typical values: RE/RL = 1.0--3.0, XE/XL = 2.0--4.0.
Some Schneider relays (e.g. P437) use a phase-only ground loop computation where the compensated current is computed differently:
Phase-only ground loop
Where
In the phase-only method, k_G has a DIFFERENT numerical value than k_0 for the same line, because the computation formula is structurally different.
Compare with the standard method where the residual current is used: . The phase-only method only uses the faulted phase current, which avoids reliance on the other two phases but requires a different compensation value.
The six algorithms represent a spectrum of complexity and accuracy. The following diagram and table summarise their relative strengths.
With fault resistance present, the simple reactance method overestimates the distance because the resistive component of V/I contaminates the measurement. Takagi and Modified Takagi use superimposed and zero-sequence currents respectively to cancel the fault resistance effect.
| Method | RF Handling | Data Required | Best For |
|---|---|---|---|
| Reactance | Assumes in-phase IS/IF | None (always available) | Bolted faults, quick estimate, fallback |
| Takagi | Eliminates via superimposed current | Pre-fault phasors | General-purpose, best single-source method |
| Modified Takagi | Eliminates via zero-sequence current | Ground fault (I0 > 0) | Ground faults without pre-fault data |
| Eriksson | Solves quadratic using source Z | Pre-fault + source impedances | Non-homogeneous systems, strong infeed |
| Novosel | Iterative with distribution factor | Source impedances | All fault types, explicit RF estimate |
| Radial | Includes RF in distance (no separation) | None (always available) | Bolted faults on radial feeders, quick sanity check |
Cross-Validation
Each algorithm produces a time-varying distance estimate across the fault window. The per-sample estimates are summarised using robust statistical measures. The median distance is the headline result because it is resistant to outliers — a few extreme samples (from DFT transients or CT saturation) do not shift the result. The spread is quantified using the Median Absolute Deviation (MAD).
Median fault distance
Where
Median Absolute Deviation (MAD)
Where
MAD is converted to a standard-deviation-equivalent (σ) by multiplying by 1.4826, which assumes an underlying normal distribution.
Robust sigma
Where
The confidence level is determined by comparing the MAD to the line length. This produces a percentage that scales naturally with the protected line — a 0.5 km spread on a 10 km line is significant, but the same spread on a 200 km line is excellent.
| MAD / Line Length | Confidence | Interpretation |
|---|---|---|
| < 5% | High | Consistent measurements with low scatter. Distance estimate is reliable. |
| 5% – 15% | Medium | Moderate scatter. Distance estimate is usable but should be interpreted with caution. |
| > 15% | Low | High scatter. Distance estimate has significant uncertainty. Check for CT saturation, incorrect line parameters, or evolving faults. |
Fallback When Line Length Is Not Set