IDMT curve equations, time multiplier mathematics, coordination principles, and standards references.
In Detego
The Inverse Definite Minimum Time (IDMT) characteristic defines the relay operating time as a function of the current multiple . The key property is that operating time decreases as current increases -- an "inverse" relationship. This allows relays at different locations to coordinate by time alone: a relay closer to the fault sees higher current, operates faster, and clears the fault before the upstream relay times out.
The current multiple (also called the plug setting multiple or PSM) is the ratio of the measured fault current to the pickup current:
Current multiple
Where
The relay only starts timing when Ir > 1 (current exceeds pickup). Below pickup, the operating time is infinite -- the relay does not operate.
Both IEC and IEEE curves can be expressed with a single unified formula. IEC curves have , while IEEE curves have a non-zero additive constant that produces subtly different coordination behaviour at high multiples:
Unified IDMT operating time
Where
For Definite Time (DT) curves: t = TMS regardless of current (flat time). Set TMS = 0 for instantaneous operation.
The denominator creates an asymptote at -- operating time approaches infinity as current approaches the pickup value. For Standard Inverse (p = 0.02), the curve is nearly flat at high multiples; for Extremely Inverse (p = 2), the curve drops very steeply, making it suitable for fuse coordination.
The TMS is a linear scaling factor that shifts the entire curve up or down without changing its shape. Doubling TMS doubles all operating times; halving TMS halves them. This allows fine-tuning of coordination margins between relays:
DT Stages
The IEC 60255-151 standard defines four inverse-time curves plus a definite-time option. The IEC formula has no additive constant ():
Where
| Curve | A | p | t @ Ir=2 | t @ Ir=10 | Typical Application |
|---|---|---|---|---|---|
| Standard Inverse (SI) | 0.14 | 0.02 | 10.02 s | 2.97 s | General purpose -- most common worldwide. Good for networks where fault current does not vary significantly with location. |
| Very Inverse (VI) | 13.5 | 1 | 13.50 s | 1.50 s | Networks where fault current varies significantly with distance to the fault. Better discrimination than SI for variable fault levels. |
| Extremely Inverse (EI) | 80 | 2 | 26.67 s | 0.81 s | Fuse coordination in distribution feeders. The steep curve closely matches fuse melting characteristics. |
| Long-Time Inverse (LTI) | 120 | 1 | 120.0 s | 13.33 s | Thermal overload protection. Very slow operation tolerates long overloads without nuisance tripping. |
| Definite Time (DT) | -- | -- | TMS | TMS | Flat operating time: regardless of current magnitude. Used for high-set and instantaneous stages. |
Why SI Is So Common
The IEEE C37.112 standard defines three inverse-time curves using the unified formula with a non-zero additive constant . The IEEE curves produce slightly different coordination behaviour at high current multiples compared to IEC curves.
Where
| Curve | A | B | p | IEC Equivalent |
|---|---|---|---|---|
| Moderately Inverse | 0.0515 | 0.114 | 0.02 | Similar to IEC SI, but with a finite minimum time at high currents |
| Very Inverse | 19.61 | 0.491 | 2 | Similar to IEC EI, with steeper drop and different asymptotic behaviour |
| Extremely Inverse | 28.2 | 0.1217 | 2 | Very steep inverse -- well-suited for fuse coordination on US distribution |
IEC vs IEEE
The diagram below shows all seven IDMT curves at TMS = 1.0 on a log-log scale. The X-axis is the current multiple and the Y-axis is the operating time in seconds. Key observations:
IDMT curve family at TMS = 1.0. IEC curves (solid) follow t = TMS × A / (Irp − 1). IEEE curves (dashed) add a constant B: t = TMS × (A / (Irp − 1) + B). All curves approach infinity as Ir → 1 (the pickup asymptote).
CT ratio scaling
Where
Example: 1000/1 CT with measured 4.5 A secondary -> 4500 A primary.
The residual current (also called neutral current or zero-sequence current) is the vector sum of all three phase currents. In a balanced system, the residual current is zero. During an earth fault, the faulted phase carries additional current that returns through earth, creating a non-zero residual.
Residual current
Where
The residual current is computed sample-by-sample, then RMS-processed like a phase current. This ensures the earth fault stages see the same measurement as a real IDMT relay connected to a residual CT.
Detego evaluates protection operating points by measuring the RMS fault current at a specific time and computing the IDMT operating time for each configured stage.
The operating point is evaluated at the measurement time, which is determined in this order of priority:
For each phase (A, B, C) and each configured stage, Detego computes:
Stage evaluation
Where
After evaluating all stages, Detego identifies the fastest stage for each phase -- the stage with the minimum operating time. This is the stage that would trip first in a real relay.
Earth fault stages are evaluated identically, but against the residual current RMS instead of phase currents.
When multiple stages are configured, they form a composite protection characteristic -- the effective operating time at any current level is the minimum of all individual stage times. Detego renders this composite on the TCC chart as a composite curve.
A stage is dominated at a particular current level if another stage produces a faster operating time. The composite curve logic:
Multi-stage TCC coordination: S1 (IEC Standard Inverse, 200 A, TMS 0.3) handles moderate faults; S2 (Definite Time instantaneous, 2000 A) provides fast clearance for high-current faults. The composite curve transitions from S1 to S2 via a vertical connector at the S2 pickup current. Operating points show per-phase fault currents plotted on the fastest-tripping stage.
When coordinating multiple relays in series, the upstream relay must be slower than the downstream relay by a sufficient grading margin at every current level. The required margin accounts for:
Minimum grading margin
Where
A typical fixed grading margin of 300-400 ms is often used as a simplified approach when detailed relay and breaker data is not available.
Consider a relay with the following settings:
A COMTRADE recording shows a phase A fault current of 4500 A primary.
S1 operating time
Since 4500 A > 2000 A (S2 pickup), S2 picks up with: (instantaneous).
S2 is faster (0 s vs 0.659 s), so the relay trips on S2 instantaneously. On the TCC chart, the Phase A operating point marker appears on the S2 horizontal line at 4500 A, labelled "INST".
Practical Note
Detego uses an adaptive two-zone sampling strategy to generate smooth IDMT curves on the log-log TCC chart. This is necessary because the curve has an asymptote at where the slope approaches infinity, and a nearly flat region at high multiples.
Times exceeding the maximum display limit are capped (not discarded), which produces a visual vertical asymptote on the chart. 400 points per curve provides smooth rendering at all zoom levels.
| Standard | Relevance |
|---|---|
| IEC 60255-151 | Defines the four IEC IDMT curves (SI, VI, EI, LTI) and the DT characteristic. Specifies timing tolerances (Class 5 = +/-5%). |
| IEEE C37.112 | Defines the three IEEE IDMT curves (MI, VI, EI) with the additive constant B formula. Standard in North American practice. |
| IEC 60255-1 | General requirements for measuring relays and protection equipment. Defines terms like pickup, dropout, TMS, and IDMT. |
| IEC 61850-7-4 | Defines logical nodes for overcurrent protection (PTOC) in modern IEC 61850-based substation automation systems. |