Analyze transformer differential (87T) protection with operate/restraint characteristics.
The Differential tab analyzes transformer differential (87T) protection by computing operate and restraint currents from HV and LV side measurements. It plots each time sample on an operate/restraint scatter chart to show whether the operating point falls inside the trip zone (internal fault) or the restraint zone (through-fault / load).
Access the Differential tab by clicking the scale icon in the left sidebar. The tab requires sign-in.
All settings are accessible from the gear icon in the chart header. They are organized into collapsible sections in the right-hand settings panel.
| Setting | Description |
|---|---|
| Data Source | Toggle between Compute (calculate from raw channels) and Existing (use pre-computed Idiff/Ibias). Always visible in the chart header. |
| Channel Pairs | Per-phase Side 1 / Side 2 current channel dropdowns. Auto-detected from COMTRADE naming patterns. |
| Add Winding | Per-phase button to add a tertiary (Side 3) channel for 3-winding transformers. |
| Add Phase | Add additional phase pairs (up to A, B, C). |
The entire Signal section is hidden in 3-winding mode — polarity is forced to summation and the bias factor applies as-is.
| Setting | Description |
|---|---|
| Bias Factor | Scalar multiplier for sum-based bias. Common values: 0.5 (half-sum, Schneider/SEL-587) or 1.0 (full-sum, SEL-787/Siemens 7UT6x). Auto-set when a relay type is selected. Disabled when the selected relay uses max-based bias (Siemens 7UT87, ABB/Hitachi, GE T60). |
| CT Polarity | Subtractive (I1−I2) or additive (I1+I2). Auto-detected from pre-fault waveform analysis. |
| Setting | Description |
|---|---|
| Enable Compensation | Master toggle for TAP normalization and vector group correction. |
| Rated MVA | Transformer rated apparent power. Used with winding voltages to compute TAP values. |
| HV / LV / TV Voltage (kV) | Rated winding voltages. TV voltage appears when 3-winding channels are configured. |
| Vector Group | HV-to-LV vector group (11 options). Determines the phase-shift compensation matrix. |
| TV Vector Group | HV-to-TV vector group. Appears only for 3-winding configurations. |
| Compensate Side | Which side receives the phase-shift matrix: Auto (LV), Side 1 (HV), or Side 2 (LV). |
| Zero-Seq Filter | Per-winding checkboxes (HV, LV, TV). Auto-defaulted based on vector group grounding. |
| Setting | Description |
|---|---|
| Show on Chart | Toggle the characteristic curve overlay on the scatter chart. |
| Relay Type | Grouped by manufacturer (SEL, Schneider, Siemens, ABB/Hitachi, GE) with 9 built-in relay families plus Custom piecewise-linear. Selecting a relay auto-populates its default settings and sets the correct bias method. |
| Setting | Description |
|---|---|
| Detected | Checkboxes for digital channels auto-detected by matching "trip" in the channel name (case-insensitive). All detected channels are pre-selected. |
| Add other channel | Dropdown to manually select any digital channel not auto-detected (e.g., CB52a breaker contacts). |
| Remove | Trash icon on manually-added channels to remove them from the overlay. |
The main visualization is a scatter chart plotting differential current () on the Y-axis against bias current () on the X-axis. The percentage bias characteristic curve divides the chart into two regions:
The percentage bias characteristic shape depends on the selected relay type: most use a dual-slope or triple-slope curve with a flat minimum pickup at low bias levels, progressively steeper slopes at higher bias levels for CT saturation stability, and an optional unrestrained threshold shown as a dashed horizontal line.
When trip signals are selected in settings, colored “T” badges appear on the scatter chart at the trajectory point where each digital channel first changed state. Each trip channel is assigned a distinct color. The badges are playback-aware — they only appear once the animation reaches the trip time.
Compute mode — Select raw current channels for each side. Detego applies TAP normalization, vector group phase shift, and polarity correction to compute the differential and bias quantities from scratch.
Pre-computed mode — Select differential and bias channels directly from the COMTRADE channel list. This uses the relay's own internal calculations as-is. The Compute/Existing toggle is always available in the chart header — useful when auto-detection does not find pre-computed channels but you know they exist in the file.
Detego automatically detects CT polarity using cross-correlation analysis between HV and LV current waveforms. Positive correlation means currents flow in the same direction (subtractive polarity); negative correlation means opposite directions (additive polarity).
If auto-detection produces incorrect results (e.g., very low load current or unusual CT wiring), you can manually toggle the polarity in the settings.
In 3-winding mode, polarity auto-detection is disabled and the Signal section is hidden — all three winding currents are always summed.
Each phase pair has an + Add winding button that opens a Side 3 (tertiary) channel dropdown. When all phases have tertiary channels assigned, the tab enters 3-winding mode:
If any phase is missing its tertiary channel, the tab falls back to 2-winding behavior for all phases.
The Relay Type dropdown is grouped by manufacturer. Selecting a relay auto-populates default settings from the relay manual and sets the correct bias method (sum or max). Each relay family uses its native setting names so values can be entered directly from the relay's settings printout.
SEL
Schneider
Siemens
ABB / Hitachi Energy
GE
Custom
When a characteristic curve is configured, per-phase verdict cards appear in the settings panel showing one of three classifications:
Practical Tips
How it works