Configure impedance-based fault location on the R-X plane.
The Distance tab lets you overlay zone boundaries on an R-X impedance plane and plot measured fault impedance loci from your COMTRADE recording. It answers the key question: "Did the fault impedance fall inside a protection zone, and which zone would have operated?"
You configure the protected line's impedance, choose between Mho (circular) or Polygonal (quadrilateral) zone shapes, set per-zone reach values to match your relay settings, and then see the measured impedance trajectory traced against those zones in real time as you move the cursor through the recording.
Getting Started
All settings are accessible from the gear icon in the Distance tab header. Each parameter is described below with its effect on the R-X display and impedance computation.
These parameters define the protected line's electrical characteristics. They are the foundation for all zone reach calculations and the R-X plane orientation.
| Parameter | Unit | Description |
|---|---|---|
| Z1 mag | Ohm | Positive-sequence line impedance magnitude. Sets the length of the dashed Z1 vector drawn on the R-X chart and is used for K0 computation. Typical values: 1-50 Ohm for transmission lines (secondary side). |
| Z1 ang | deg | Positive-sequence impedance angle (line angle). Controls the direction of the dashed Z1 vector on the R-X plane and serves as the default alpha when adding new polygonal zones. Typical values: 60-85 deg for overhead lines, 20-70 deg for cables. |
| Z0 mag | Ohm | Zero-sequence impedance magnitude. Only used to compute the K0 compensation factor for ground fault loops (AG, BG, CG). Does not affect zone shapes. Typically 2.5-4x Z1 for overhead lines, 1.5-2.5x for cables. |
| Z0 ang | deg | Zero-sequence impedance angle. Only used for K0 computation. Typically 5-15 deg less than Z1 angle. |
| RCA | deg | Relay Characteristic Angle. Serves as the default alpha when adding new Mho zones. Each zone now has its own alpha angle that can be set independently. Has no effect on polygonal zones. Typically set to Z1 angle minus 5 deg. |
Per-Zone alpha Angle
Choose between two zone boundary shapes:
Each zone is defined by the following parameters. Values are entered directly in ohms -- matching the settings sheet of any relay (Siemens P437, ABB REL670, GE D60, SEL-421, etc.). You can add or remove zones freely.
| Parameter | Unit | Mode | Description |
|---|---|---|---|
| |Z| / X | Ohm | Both | Zone reach in ohms. In Mho mode this is the circle diameter (|Z| reach); in Polygonal mode it is the reactance reach (X-reach). Enter the value directly from the relay settings sheet. |
| Dir | -- | Both | Zone direction: Forward or Reverse. Forward zones look into the protected line; reverse zones look behind the relay for busbar backup or blocking schemes. |
| alpha | deg | Both | Per-zone characteristic angle. In Mho mode, tilts the circle. In Polygonal mode, tilts the resistance boundaries. Defaults to Z1 angle (polygonal) or RCA (Mho) when a new zone is added. |
| ms | ms | Both | Trip time delay. 0 = instantaneous (Zone 1). Display label for reference -- does not affect zone geometry on the chart. |
| R-phi | Ohm | Polygonal | Resistance reach for phase-phase faults. Measured perpendicular to the alpha direction. Used when any phase-phase loop (AB, BC, CA) is active. |
| Rg | Ohm | Polygonal | Resistance reach for phase-ground faults. Used when any ground loop (AG, BG, CG) is active. Typically 1.3x the phase R-reach. |
| sigma | deg | Polygonal | Reactance boundary tilt angle. Tilts the top and bottom boundaries of the polygonal zone. 0 deg = horizontal boundaries (classic parallelogram). Negative values tilt the right side of the reactance boundary downward. |
Phase vs Ground R-reach
The load encroachment circle shows the minimum expected load impedance boundary. Set Z_load to a positive value (in Ohm) to display a dashed circle centered at the origin on the R-X plane. If any zone boundary overlaps this circle, there is a risk of the relay tripping on normal load current.
Set Z_load to 0 (default) to disable the circle. This setting is found in the "Load Encroachment" section of the settings sidebar.
CT and VT ratios scale the computed impedance from secondary (relay) quantities to primary (system) quantities. The ratio VT/CT is applied to all impedance measurements. If your COMTRADE data is already in primary quantities, set both ratios to 1:1.
Distance relays use multiple zones with progressively increasing reach and time delay to provide both fast clearance for close-up faults and backup protection for remote faults.
| Zone | Typical Reach | Time Delay | Purpose |
|---|---|---|---|
| Zone 1 | 8 Ohm (~80% of Z1) | Instantaneous | Primary fast protection. Set below 100% of line impedance to prevent overreach from CT/VT errors and line parameter uncertainty. |
| Zone 2 | 12 Ohm (~120% of Z1) | 350 ms | Covers the remaining line plus the remote bus. Time-graded to coordinate with Zone 1 of the adjacent line. |
| Zone 3 | 20 Ohm (~200% of Z1) | 800 ms | Remote backup for adjacent line sections. Must be checked against minimum load impedance to avoid load encroachment trips. |
| Reverse | 2 Ohm (reverse) | Instantaneous | Reverse-looking zone for busbar backup or blocking schemes. Covers faults behind the relay location. Shown with dashed lines on the R-X chart. |
Load Encroachment
A distance relay simultaneously monitors six fault loops to detect all possible fault types. Toggle loops on/off using the colored chips in the Distance tab header. The faulted loop (lowest impedance near fault time) is highlighted with a pulse animation.
Loop Chip States
| Loop | Type | Fault Types Covered |
|---|---|---|
| AB | Phase | A-B and A-B-G faults |
| BC | Phase | B-C and B-C-G faults |
| CA | Phase | C-A and C-A-G faults |
| AG | Ground | A-G fault (uses K0 compensation) |
| BG | Ground | B-G fault (uses K0 compensation) |
| CG | Ground | C-G fault (uses K0 compensation) |
Loop Selection and Zone Width
The main chart shows the R-X impedance plane with zone boundaries and impedance loci. Key visual elements:
The readout bar at the bottom shows the numerical impedance (R, X, |Z|, angle) for each active loop at the cursor position, plus a zone indicator if the point is inside any zone boundary.
Tips for Common Configurations
How it works